Designation codes

According to CEI 20-27

Designation groups

Designation

Symbol

Reference to standards Harmonised cable H
Authorised national cable A
Other national cable types N
Rated voltage Uo/U 100/100 V 01
300/300 V 03
300/500 V 05
450/750 V 07
0,6/1 kV 1
Insulation material ordinary PVC V
PVC for temperature of 90°C V2
Synthetic rubber for temperature of 60°C R
Ethylene propylene rubber B
Polychloroprene for welding cables N2
Polyolefin-based cross-linked compound with low smoke, toxic and corrosive gases emissions Z
Polyolefin-based thermoplastic with low smoke, toxic and corrosive gases emissions Z1
Metallic coatings
(shielding and armouring)
Copper braid shield applied around assembled cores C4
Copper braid shield applied around single cores C5
Copper wire, tape, or strip screen over assembled cores C7
Concentric copper conductor C
Steel wire armour Z 2
Flat steel wire armour Z 3
Steel tape armour Z 4
Steel wire braid armour Z 5
Cable shape Flat non separable cables H2
Flat cables with three or more cores H6
Cables with double layer insulation applied by extrusion H7
Jacket material ordinary PVC V
PVC for operating temperature of 90°C V2
Oil resistant PVC V5
Synthetic rubber R
Ethylene propylene rubber B
Polychloroprene N
Water resistant polychloroprene N8
Polyurethane Q
Chlorosulfonated polyethylene or chlorinated polyethylene N4
Polyolefin-based cross-linked compound with low smoke, toxic and corrosive gases emissions Z
Polyolefin-based thermoplastic with low smoke, toxic and corrosive gases emissions Z1
Conductor material Copper None
Aluminium A
Conductor form Rigid round, solid U
Rigid round stranded R
Flexible for dynamic laying F
Flexible for fixed laying K
Flexible for welding cables D
Highly flexible for welding cables E

Secondo tabella CEI UNEL 35011-36011 (ove applicabile)

Designation groups

Designation

Symbol

Conductor type Copper None
Aluminium A
Conductor form Rigid round, solid U
Rigid round stranded R
Flexible round stranded F
Highly flexible round stranded FF
Extra flexible round stranded or special construction EF
Insulation material PVC for operating temperature of 70°C R
PVC for operating temperature of 70°C of superior quality (anti-aging) R2
PVC for operating temperature of 90°C R7

PVC-based insulation compound with a characteristic temperature of 70° C (CPR)

S17
Synthetic rubber for temperature of 60°C G
High modulus ethylene propylene rubber G7
Elastomeric compound with low smoke, toxic and corrosive gas emission G9
Elastomeric compound with low smoke, toxic and corrosive gas emission G10
High modulus ethylene propylene rubber-based compound with low development of fumes and acidity with a characteristic temperature of 90°C (CPR) G16
Crosslinked elastomeric compound with low development of fumes and acidity, suitable for cables without protective coating, with a characteristic temperature of 90°C (CPR) G17
Crosslinked elastomeric compound with low development of fumes and acidity, with a characteristic temperature of 90°C (CPR) G18
Thermoplastic compound with low smoke, toxic and corrosive gas emission M9
Plastic material with low toxic and corrosive gas emission (36011) M
Cross-linked compound with low smoke, toxic and corrosive gas emission G21
Thermoplastic polyethylene E
Cross-linked polyethylene for temperatures of 85°C E4
One or more mica tape strips or closed glass braid T
Cable shape Cores arranged for round cable O
Cores laid parallel for flat cable D
Helically wound cores X
Metallic coatings
(shielding and armouring)
Shield made of aluminium or metallised paper tape H
Copper tape, flat strip, or wire shield H1
Stranded or braided copper shield H2
Double-strand or braided copper shield H3
Concentric copper conductor C
Concentric aluminium conductor AC
Stranded or braided metallic armouring A
Steel wire armour F
Flat steel wire armour Z
Steel tape armour N
Jacket material TM1, TM2, RZ type PVC R
PVC-based thermoplastic compound (CPR) R16
Ez type linear polyethylene E
Cross-linked polyethylene, quality E4M E4
Synthetic rubber, quality Gy G
Polychloroprene, quality Ky, Kn or Kz K
Plastic material with low toxic and corrosive gas emission (36011) M
Thermoplastic compound with low smoke, toxic and corrosive gas emission M1
Elastomeric compound with low smoke, toxic and corrosive gas emission M2
Elastomeric compound with low smoke, toxic and corrosive gas emission M3
Thermoplastic compound with low development of fumes and acidity (CPR) M16
Elastomeric compound with low development of fumes and acidity (CPR) M18
Cross-linked compound with low smoke, toxic and corrosive gas emission M21



Key reference standards

CEI and EN Standards

Standard

Description

CEI 11-17 Specifies generation, transmission, and public distribution systems of electric energy. Underground lines from 1 to 45 kV.
CEI 20-13
(IEC 60502-1 as applicable)
(IEC 60502-2 as applicable)

Specifies the construction requirements, testing methods and requirements for type R, R16, E, M1,M2, M16, M18, G7, G16, K insulated cables, for operating voltages from 1kV up to 3 kV.

CEI 20-16 Specifies the test procedure for the determination of partial discharge for medium voltage cables.
CEI 20-20/5

Specifies the construction requirements, testing methods and requirements for PVC insulated cables sheathed PVC, for mobile service, with operating voltages up to 450/750 V.

CEI 20-21 Specifies the calculation of the current rating of power cables in steady condition.
CEI 20-22/2
(CEI 20-22 II)

Specifies the test procedure and requirements for assessment of flame spread of bundled cables, with non-metallic material of 5 or 10 kg/m.

(CEI 20-22 III)
IEC 60332-3-24 Cat. C

Specifies the test procedure for the assessment of flame spread of bundled cables, with non-metallic material of 1.5 l/m.
CEI 20-27 Specifies the designation system for harmonized cables.
CEI 20-37/4-0

Specifies the test equipment and method for the determination of the toxicity index of gases released during combustion of materials from cables.

CEI 20-38

Specifies the construction requirements, test methods of G10 insulated cables which do not propagate fire and generate low levels of toxic and corrosive gases (halogen-free), for operating voltages up to 1kV.

CEI 20-45

Specifies the construction requirements, testing methods and requirements for fire resistant cables, for operating voltages from 1kV up to 3 kV.

CEI 20-48 Specifies the general requirements for high modulus EPR insulated cables for distribution, with operating voltage of 0.6/1 kV.
CEI 20-67 Provides guidance on using electric cables with an operating voltage up to 0.6/1 V.
CEI 64-8 Electrical systems at a rated voltage not exceeding 1,000 V AC and 1,500 V DC.
CEI 64-15 Electrical systems in buildings of historic and/or artistic importance.
EN 50200

Specifies the equipment and method of test for the resistance to fire of cables having a diameter of up to 20 mm. Method with mechanical shock.

EN 50267-2-1
(IEC 60754-1 as applicable)
Specifies the test method for the determination of corrosive gases (HCI) released during combustion of materials from cables.
EN 50267-2-2

Specifies the test procedure for the determination of degree of acidity (corrosivity) of gases, released during combustion of materials from cables, by measuring Ph and conductivity.

EN 50334 Specifies the methods for marking by inscription for the identification of cores of electric cables.
EN 50336

Specifies the technical characteristics and test requirements for insulation and sheath compounds of power and signalling cables.

EN 50362 Specifies the equipment and method of test for the resistance to fire of cables having a diameter greater than 20 mm. Method with mechanical shock.
EN 50395
EN 50396

Specifies the test methods and requirements of harmonised cables insulated in PVC and rubber with operating voltage up to 450/750 V.

EN 50399 Describes the test methods for the evaluation of the vertical propagation of the flame, thermal release, smoke production, and the presence of inflamed particles/droplets on the cables or wires. The method allows for classification according to the Construction Products Regulation (CPR).
EN 50414
(CEI 20-85)
Describes the procedure for the analysis of lead in the PVC.
EN 50525-1
(CEI 20-107)
Describes the general requirements for electric cables with operating voltage up to 450/750 V.
EN 50525-2-11 It is applied to flexible cables with thermoplastic PVC insulation and PVC sheathing. These are cables with a nominal voltage Uo/U no greater than 300/500 V. The cables are for connecting domestic appliances to the fixed power supply. Circular and flat cables are included.
EN 50525-2-21 It is in regards to the particular specifications for flexible cables insulated with crosslinked elastomeric compound and undersheating with reticulated elastomeric compound or thermoplastic polyurethane (TPU), with a nominal voltage of up to 450/750 V.
EN 50525-2-31 Describes the construction requirements, methods, and the test requirements for single-core cables without sheathing, with PVC thermoplastic insulation with maximum temperature in continuous service of 70 and 90° C, for fixed wiring, with operating voltage up to 450/750 V.
EN 50525-2-51 Applies to oil-resistant flexible cables with insulation and PVC sheathing. Shielded and unshielded types are included. These cables have a nominal voltage Uo/U no greater than 300/500 V. The cables are intended for interconnection of the production machines. The maximum temperature in continuous service for cables in this standard is 70° C.
EN 50525-3-31 It applies to single-core cables without sheathing, insulated with halogen-free thermoplastic compound and low emission of fumes and corrosive gases when exposed to fire, for fixed wiring and at a maximum service temperature of 70° C. These cables have a nominal voltage Uo/U not higher than 450/750 V. For cables with rated voltage 450/750 V there are two types: Type 1 and Type 2
EN 50525-3-41

Concerns the construction and testing requirements for single-core electric cables without sheathing and with halogen-free crosslinked insulation, suitable for fixed installations with particular fire behaviour characteristics. Nominal voltage up to 450/750 V.

EN 50565-1
(CEI 20-40/1)
Vides guidance on using electric cables with an operating voltage up to 450/750 V.
EN 50618 Describes the construction requirements, methods and test requirements for insulated and sheathed cables in the LS0H crosslinked compound. Indicated for photovoltaic systems with a nominal operating voltage no greater than 1000 V in ac and 1500 V in dc.
EN 60216-1 Specifies the ageing conditions and procedures to be used for deriving thermal endurance characteristics of materials.
EN 60332-1-2
(IEC 60332-1-2)
Specifies the test procedure and requirements for the assessment of the vertical flame propagation on single cables.
EN 60754-2 Describes the procedure for determining the potential corrosivity of the gases emitted during the combustion of materials taken from electric cable constructions by measuring the acidity (pH) and the conductivity of an aqueous solution resulting from the gases emitted during combustion.
EN 61034-2 Describes the testing procedure for determining the smoke density emitted by the cables subjected to combustion. (Optical transmittance)


CEI UNEL Standards

Table

Description

UNEL 00721 Specifies the sheathing colours of electric cables.
UNEL 00722 Specifies the identification of cores in electric cables.
UNEL 35011 Specifies the electric cable designation symbols for energy, signal and control for national cables.
UNEL 35012 Specifies the markings and classification of cables in relation to fire.
UNEL 35016 Describes the requirements of the Classes of reaction to fire of cables in relation to EU Regulation "Construction Products Regulation" (305/2011)
UNEL 35024/1

Specifies the continuous current capacities for open air installation of power cables with operating voltages up to 1,000 V AC and 1,500 V DC

UNEL 35026

Specifies the continuous current capacities for underground installation of power cables with operating voltages up to 1,000 V AC and 1,500 V DC

UNEL 35027 Specifies the continuous current capacity for open air and underground installation of medium voltage power cables.
UNEL 35310 Describes the construction and size requirements of the 450/750 V electric cables insulated in G17 quality elastomeric rubber, with special fire-reaction characteristics and in compliance with the Construction Products Regulation (CPR). Single-core cables without sheathing and with flexible conductors. Reaction to fire class: Cca-s1b,d1,a1. Type FG17
UNEL 35318 Describes the construction and size requirements of the 0.6/1kV electric cables insulated in high quality G16 ethylene propylene rubber with PVC undersheating, with special fire-reaction characteristics and in compliance with the Construction Products Regulation (CPR). Single- or multi-core cables with flexible conductors for fixed wiring, with or without shielding. Reaction to fire class: Cca-s3,d1,a3. Type FG16(O)R16, FG16OH1R16, FG16OH2R16
UNEL 35322 Describes the construction and size requirements of the 0.6/1kV cables for signalling and control, insulated in high quality G16 ethylene propylene rubber with PVC undersheating, with special fire-reaction characteristics and in compliance with the Construction Products Regulation (CPR). Multi-core cables with flexible conductors for fixed wiring, with or without shielding. Reaction to fire class: Cca-s3,d1,a3. Type FG16OR16, FG16OH1R16, FG16OH2R16
UNEL 35324 Describes the construction and size requirements of the 0.6/1kV electric cables insulated in high quality G16 ethylene propylene rubber with M16 quality thermoplastic undersheating, with special fire-reaction characteristics and in compliance with the Construction Products Regulation (CPR). Single- or multi-core cables with flexible conductors for fixed wiring, with or without shielding. Reaction to fire class: Cca-s1b,d1,a1. Type FG16(O)M16, FG16OH1M16, FG16OH2M16
UNEL 35328 Describes the construction and size requirements of the 0.6/1kV cables for signalling and control, insulated in high quality G16 ethylene propylene rubber with M16 quality thermoplastic undersheating, with special fire-reaction characteristics and in compliance with the Construction Products Regulation (CPR). Multi-core cables with flexible conductors for fixed wiring, with or without shielding. Reaction to fire class: Cca-s1b,d1,a1. Type FG16M16, FG16OH1M16, FG16OH2M16
UNEL 35368 Describes the construction and size requirements of 450/750 V electric cables insulated with halogen-free fire retardant elastomeric rubber. Single-core cables without sheathing and with flexible conductors. Type N07G9-K
UNEL 35369 Describes the construction and size requirements of 0.6/1 kV electric cables insulated with halogen-free fire retardant elastomeric compound. Cables with flexible conductors for fixed wiring. Type FG10OM1.
UNEL 35370 Describes the construction and size requirements of 0.6/1 kV electric cables insulated with halogen-free fire retardant elastomeric compound. Cables with rigid conductors for fixed wiring. Type RG10OM1.
UNEL 35371 Describes the construction and size requirements of 0.6/1 kV cables for signalling and control, insulated with halogen-free fire retardant elastomeric compound. Multi-core flexible for fixed wiring. Type FG10OM1.
UNEL 35375 Describes the construction and size requirements of 0.6/1 kV electric cables insulated in high quality G7 ethylene propylene rubber, PVC sheathing, fire retardant and with reduced halogen emission. Single- or multi-core with flexible conductors for fixed wiring, with or without shielding. Type FG7(O)R, FG7OH1R, FG7OH2R.
UNEL 35376 Describes the construction and size requirements of 0.6/1 kV electric cables insulated in high quality G7 ethylene propylene rubber, PVC sheathing, fire retardant and with reduced halogen emission. Single and multi-core with rigid conductors for fixed wiring. Type UG7(O)R, RG7(O)R.
UNEL 35377 Describes the construction and size requirements of 0.6/1 kV cables for signalling and control, insulated in high quality G7 ethylene propylene rubber, PVC sheathing, fire retardant and with reduced halogen emission. Multi-core with flexible conductors for fixed wiring, with or without shielding. Type FG7OR, FG7OH1R, FG7OH2R.
UNEL 35379 Describes the construction and size requirements of 0.6/1 kV electric cables insulated in high quality G7 ethylene propylene rubber, PVC sheathing, fire retardant and with reduced halogen emission. Multi-core with rigid conductors, reinforced with steel strips. Type U/RG7ONR
UNEL 35382 Describes the construction and size requirements of 0.6/1 kV electric cables insulated in high quality G7 ethylene propylene rubber, M1 thermoplastic undersheating, fire retardant and halogen-free. Single- or multi-core cables with flexible conductors for fixed wiring, with or without shielding. Type FG7(O)M1, FG7OH1M1, FG7OH2M1.
UNEL 35384 Describes the construction and size requirements of cables for signalling and control, type FG7OM1-0.6/1 kV, FG7OH1M1-0.6/1 kV, FG7OH2M1-0.6/1 kV.
UNEL 35716 Describes the construction and size requirements of the 450/750 V electric cables insulated in S17 PVC, with special fire-reaction characteristics and in compliance with the Construction Products Regulation (CPR). Single-core cables without sheathing and with flexible conductors. Reaction to fire class: Cca-s3,d1,a3. Type FS17
UNEL 35752 Describes the construction and size requirements of electric cables insulated with fire retardant PVC with reduced halogen emissions. Single-core without sheathing and with flexible conductors. Type N07V-K.
UNEL 35755 Describes the construction and size requirements of 0.6/1 kV cables for signalling and control, insulated in PVC, with PVC sheathing, fire retardant and with reduced halogen emission. Multi-core with flexible conductors for fixed wiring, with or without shielding. Type N1VV-K, N1VC7V-K, N1VC4V-K.
UNEL 35756 Describes the construction and size requirements of 0.6/1 kV electric cables insulated in PVC, with PVC sheathing, fire retardant and with reduced halogen emission. Multi-core with flexible conductors for fixed wiring, with or without shielding. Type N1VV-K, N1VC7V-K, N1VC4V-K.
UNEL 35757 Describes the construction and size requirements of 0.6/1 kV electric cables insulated in PVC, with PVC sheathing, fire retardant and with reduced halogen emission. Single-core cables with flexible conductors for fixed wiring. Type N1VV-K
UNEL 36713 Specifies construction and sizing requirements for internal telephone cables type TR/R and TR/HR.

Our Company

Since 1965, La Triveneta Cavi has been one of the major players within the European market for low- and medium-voltage cables for various sectors (industry, home use, power distribution, renewable technologies). read all »


Careers with LTC

See the list of positions currently available and fill out the job application form

Direct contact

Send an email directly to our offices

Headquarter and Production Unit 1

Brendola (VI): Via Orna, 35

36040

Production unit 2, 3 and 4

Brendola (VI): Via Alcide De Gasperi, 19 36040

 

Tolentino (MC): Contrada Le Grazie, 42 62029

 

Montecchio Maggiore(VI): Via Ettore Majorana, 9/10, 36075

Logistics unit

Brendola (VI): Via Giulio Natta, 48

36040

Corporate info

La Triveneta Cavi s.p.a.
Fully paid-up share capital € 15.480.000,00
VI Bus. Reg. no. 21789
Economic and Administrative Index 197814 Tax Code 02782190157
VAT no. 01981240243 M/VI 002258